Model No: 102
End of line, weight loaded, integrated, atmospheric deflagration proof
Storagetech’s Model 102 Pressure-Vacuum Relief Valve with Integrated End-of-line Flame Arrestor provides total peace of mind to operators of storage tanks. The Model 102 ensures protection against damage through over-pressurization, implosion due to vacuum conditions, and prevents any external flame from entering the tank.
In the closed position the pressure relief pallet and diaphragm assembly are held tightly against a seal to prevent the loss of vapour to the atmosphere. As the internal pressure in the tank increases due to product filling and vapour development, and in the event that the set pressure of the unit is reached, the diaphragm will open and discharge the gas to the atmosphere. The opening set-point is selectable from a range between 1 and 28.1 W.C. (2.5 and 70 mbar), and the valve will reseal when the tank returns to a safe pressure.
The vacuum pallet and diaphragm assembly is similarly maintained in the closed position. As the internal pressure in the tank reduces, due to emptying, the balance between the tank pressure and the external atmospheric pressure changes, and when the set pressure of the unit is reached, the diaphragm opens to admit air and rebalance the internal pressure. The vacuum set-point is selectable from a range between 1 and 28.1 W.C. (2.5 and 70 mbar). The valve will reseal when the tank returns to a safe pressure.
Unlike the conventional PVRV, the Model 102 discharges vapour and takes in air through the same vent, consequently a single end-of-line flame arrestor provides protection from the potential ingress of flames emanating from an external fire.
The integral deflagration flame arrestor is designed to minimise pressure loss and with an element constructed with a <0.65mm Maximum Experimental Safe Gap is suitable for gas groups IIB and IIA.
Several features are inherent in the valve design to ensure a smooth, positive and effective operation. The body is self-draining and drip design prevents condensate from settling on seating surfaces. A diaphragm and seal manufactured from Teflon reduce the possibility of ice formation and sticky residues hindering the valve opening, while the pallet assembly moves freely on its guide post.
Standard sizes | Weight-loaded 2.5 mbar to 70 mbar |
Ambient temp | -20°C to +60°C |
Sizes | 2” to 12” 50 to 300mm |
Flanges | API Class 150 RF, DIN PN16 |
Body | Carbon steel, stainless steel, or aluminium |
Cap | Carbon steel, stainless steel, or aluminium |
Cover | Carbon steel, stainless steel, or aluminium |
Seals | Nitrile, Teflon, and Klingrit |
Pallet | Stainless steel AISI 304 |
Paint finish | 1 Powder Coating, Colour RAL 9006 2 Epoxy Paint, Colour RAL 9006 3 Customer Specification |
ISO 16852:2008 – Flame Arrestors, Performance requirements, test methods and limits of use.
API RP 2210 -Flame Arrestors for Vents of Tanks Storing Petroleum Product.
The size of the vent should be calculated in accordance with API Standard 2000 (ISO 28300) – Venting Atmospheric and Low-Pressure Storage Tanks or other international standards.
The integrity of the seal is tested for leakage in accordance with API Standard 2521 – Use of Pressure-Vacuum Vent Valves for Atmospheric Loss.
Request a Quote
Do you need a quick quotation? Fill out the below form and expect our reply soon